1. The central control unit of EXC9100 all-digital excitation system adopts the streamlined circuit construction with mainstream ARM + new FPGA chip as its core.
2. Adopting IEEE PSS-2Aaccelerating Power System Stabilizer with standard transfer function.
3. Current equalizing technology of intelligent power converter.
4. The CAN BUS technique.
5. Configuration Programming.
6. Intelligent Control Technology.
7. All-digital system.
8. Perfect friendly HMI.
9. various outlet interface.
10. Comprehensive debugging software.
11. good electromagnetic compatibility.
12. Completely independent microcomputer/analogue three-channel and two-module with redundancy configuration.
13. Multi-CPU mode,SMT and no-fan configuration is adopted in the regulator.
14. multi-course 3-dimentioned Chinese display.
15. Advanced and reliable core control device.
16. High-speed AC sampling technique
17. Independent and intelligent detection system and perfect fault detection function.
18. the high-frequency pulse train trigger technology, low residual fast Field flashing technology.
19. Intelligent power cabinet.
20. Current equalizing technology of intelligent power converter.
21. The high-voltage pulse transformer.
22. Powerful fans stop running ability.
23. Unique SCR jumper.
24. Improve communication function.
25. Intelligent commissioning.
Performance:
No.
|
Content
|
Provision
|
Performance
|
1
|
Regulators performance indicators
|
Force-excitation ceiling voltage and time
|
100MW steam turbine:1.8 times of the rated voltage.
50MW turbine : 2 times of the rated voltage.
The duration of not less than 10S.
Ceiling voltage is calculated as 80% of the terminal voltage.
|
Voltage response time
|
Less than 0.1S
|
The accuracy of the regulator
|
Less than ± 0.5%
|
Droop Range
|
Not less than ± 15%
|
Frequency and voltage droop change
|
When the frequency change of 1%, the voltage variation is not greater than ± 0.25% of rated
|
10% phase step in the condition of no load
|
Voltage overshoot amount of not more than 50% of the step, the oscillation is not more than 3 times, settling time is not greater than 10S
|
Excitation field-flashing
|
Voltage overshoot is not more than 15% of rated voltage, the oscillation is not more than 3 times, the adjustment time is not greater than 10S
|
Rated load rejection
|
Voltage overshoot is not more than 15% of rated voltage, the oscillation is not more than 3 times, the adjustment time is not greater than 10S
|
The adjustment range
|
AVR:70% to 110% rated voltage
FCRl: 20% no-load excitation current to 110% therated excitation current
|
Given speed
|
0.3%~1%/S
|
Nominal response
|
More than 50MW turbine and steam turbine 100MW of not less than two times per second rated excitation voltage, and the rest of not less than 1 times per second rated excitation voltage
|
The generator static voltage droop
|
Not more than ± 1%
|
2
|
The rectifier bridge
|
Current coefficient
|
Not less than 0.85
|
Rectifier redundancy
|
N-1
|
The maximum instantaneous value of the output voltage of the rectifier
|
1.1 times the rated excitation current, shall not exceed the amplitude of the voltage-to-ground voltage of 30%.
|
3
|
Inversion and overvoltage protection
|
Deexcitation overvoltage
|
Shall not be less than the factory test voltage to ground voltage amplitude of 30%, shall not exceed 50%.
|
ZNO
|
Chargeability of less than 60%, 20% of the capacity margin.
|
4
|
Power supply
|
Operating frequency range
|
45~82.5Hz
|
AC380V/220
|
+10%~-15%
|
DC220V/110V
|
-15%~+10%
|
5
|
System
|
Forced removal rate of excitation system
|
Not more than 0.2%
|